Questions? Feedback? powered by Olark live chat software

Honeywell Sensepoint Flammable - High Temperature

 
£405.00
 (exc VAT)
£486.00
 (inc VAT)
SKU: 2106B23

The Sensepoint High Temperature Sensor has been specifically designed for the detection of combustible gases in high temperature hazardous area locations. Typical applications include turbine enclosures and drying ovens used in solvent based printing and coating machines.

These applications require a sensor that provides reliable and stable detection allowing low level alarm settings across a wide temperature range. Utilising a specially matched pair of Honeywell poison resistant combustible gas detection elements, the Sensepoint High Temperature Sensor has a very stable baseline allowing alarm trip points to be set as low as 5% LEL across a temperature range of -55°C to +150°C (-67°F to +302°F). The gas measuring range can be configured from 0-20% LEL up to 0-100% LEL depending on the type of controller used.

The detector elements are housed in an explosion proof assembly, and provide an industry standard 3 wire mV bridge output which can be connected to a suitable control device or converted to an analog output signal via a field transmitter.

Excellent Performance
• Certified for hazardous area operation up to +150°C (+302°F)
• Alarm trip points as low as 5% LEL
• Fast speed of response
• Poison resistant detectors
• Low power consumption

Cost Effective
• Low cost disposable sensor
• Greater than 5 year typical operating life

Reliable Operation
• Thermally matched beads provide optimum accuracy and stability
• Proven technology from the World leaderin combustible gas detection

Flexibility
• Measuring ranges from 0-20% LEL to 0-100% LEL
• Wide range of accessories

Robust Construction
• 316 Stainless Steel sensor body
• ATEX/ IECEx approved design

Specification
Range: 0-20% LEL, 0-100% LEL (Control card dependent)
Minimum Alarm Level: 5% LEL
Output Signal: mV Bridge
Operating Temperature: -55°C to +150°C (-67°F to +302°F)
Operating Humidity: Continuous: 20 to 90% RH Intermittent: 10 to 99% RH
Operating Pressure: 75 to 110kPa (750 to 1100mbar)
Stability (zero): With time: Less than ±5% LEL / year - With temperature: Less than ±3% LEL - With humidity: Less than ±3% LEL - With pressure: Less than ±3% LEL
Stability (span): With time: Less than ±5% LEL / year With temperature: Less than ±4% LEL With humidity: Less than ±3% LEL With pressure: Less than ±3% LEL
Linearity: Better than ±5% fsd
Repeatability: Better than ±2% LEL
Warm-up Time: 30 minutes
Detector Operating Life: More than 5 years (typical)
Storage Life: Typically, no degredation has been observed in clean, stable conditions for up to 5 years
Power Consumption: 0.7W at 200mA
Enclosure Material: 316L Stainless Steel
Mounting Thread: M20, M25 or ¾˝ NPT
Weight: 225g (7.9oz)
Certification: ExII 2 GD Ex d IIC T3 Gb Tamb -55°C to +150°C Extb IIIC T200ºC Db IP66 A21 Baseefa08ATEX0264X IECEx BAS08.0069X